5
Be Cool! Be Aerocool!
7
.2
Over
-
Current Protection
Current protection should be designed to limit the current to operate within
safe operating conditions. Over current protection schemes where only the
voltage output that experiences the over current event is shut off may be
adequate to maintain safe operation of the power supply and the system;
however, damage to the motherboard or other system components may
occur. The recommended over current protection scheme is for the power
supply to latch into the shutdown state. The setting of over current
protection for each output rail is as following.
7
.3
Over Power Protection
The power supply will be shutdown and latch off when output power is
105%~150%.
7
.4
Over
-
Temperature Protection
This power supply includes an over-temperature protection sensor, which
can trip and shut down the power supply at 110
7
.5
Under voltage protection
In an under voltage fault occurs, the supply will latch all DC outputs into a
shutdown state when +12V,+5V & +3.3V outputs under 60% of it's
maximum value.
7
.6
Short Circuit Protection
Short circuit placed on +5V,+12V,+3.3V,-12V will latch off. +5VSB will
auto-recovery.
8. Environmental Requirements
6.1
Operating / Storage Temperature Range
Operating ambient :
0 min to +40 max
Non operating ambient :
-20 to +60
6.2
Humidity ( non condensing )
Operating ambient :
10% to 90% relative humidity
Non operating ambient :
5% to 95% relative humidity